Wincc 7.5 Sp2 Compatibility List

WinCC 7.5 SP2 is officially supported on:

👉 Avoid Windows 11 or standard Windows 10 builds. They are not certified and will cause unpredictable runtime behavior.

Pro tip: Always use the LTSC or Server SKUs. Consumer Windows = trouble.

WinCC is not a standalone application; it sits at the intersection of industrial automation (PLC communication) and IT (databases, reporting). Siemens rigorously tests specific combinations of: wincc 7.5 sp2 compatibility list

Critical Note: WinCC 7.5 SP2 dropped support for several older OS versions. Attempting to force installation on Windows 7 or Windows Server 2008 will result in the installer blocking the setup or unpredictable behavior during archiving.


WinCC uses Microsoft SQL Server for process value archiving, alarm logging, and user administration. WinCC 7.5 SP2 still relies on a dedicated MS SQL instance (not the TIA Portal integrated one).

| Use Case | Compatible SQL Version | Provided by Siemens | Notes | | :--- | :--- | :--- | :--- | | Single-station (<= 2048 tags) | SQL Server 2017 Express Edition SP2 | Included in WinCC setup | Free, limited to 10GB database size | | Server/Multi-client (> 2048 tags) | SQL Server 2017 Standard (64-bit) | User must purchase separately | Requires specific collation (Latin1_General_CI_AS) | | High Availability / Cluster | SQL Server 2017 Enterprise | User purchase | Supports failover clustering | | Redundant Servers | SQL Server 2017 Standard | User purchase | Mirroring or Always On (with restrictions) | WinCC 7

| Software | Compatibility | |----------|----------------| | STEP 7 Professional (TIA Portal) | V16, V17 | | SIMATIC NET | V15.1, V16 | | S7-1200 / S7-1500 OPC UA | Yes | | WinCC WebUX | Yes (requires configuration) | | DataMonitor / WebNavigator | Requires separate compatibility packages | | SIMATIC Logon | V1.6 SP2 or higher | | Industrial PC Image & Recovery | Yes |

Document Version: 1.0
Software Version: WinCC V7.5 SP2
Date: [Insert Date]

| Option | Compatible Version | Notes | |--------|--------------------|-------| | WinCC/WebUX | V7.5 SP2 | Requires IIS and HTTPS certificate | | WinCC/Redundancy | V7.5 SP2 | Requires Server OS + identical hardware/SQL | | WinCC/IndustrialDataBridge | V7.5 SP2 | Connects SQL to external DBs | | WinCC/Calibration | V7.5 SP2 | – | | WinCC/Audit | V7.5 SP2 + Update 3+ | For FDA compliance | | WinCC/PerformanceMonitor | V7.5 SP2 | – | 👉 Avoid Windows 11 or standard Windows 10 builds


| Source Version | Target Version | Allowed? | |----------------|----------------|-----------| | WinCC 7.4 SP1 | 7.5 SP2 | ✅ Yes (project conversion) | | WinCC 7.5 | 7.5 SP2 | ✅ Yes (Update installation) | | WinCC 7.5 SP1 | 7.5 SP2 | ✅ Yes | | WinCC 7.3 or older | 7.5 SP2 | ❌ No (must go via 7.4 SP1) |


Exclude the following processes from real-time scanning: